DESIGN OF PIPERACK STRUCTURE – ASCE 7-10
The length of Pipe rack 42m is considered to avoid forces due to thermal expansion of pipe rack under ambient temperature and free to expand at ends. This is general engineering practice for Pipe rack design with single vertical bracings and mentioned in “Design Specification for Steel Structures”
The geometry of the pipe rack structure as below
- Width of the structure 9.0m
- Length 42.0m
- Frame spacing 6.0m
- Height 20.0m.
Pipe rack consists of 3 levels of pipe support and 4 levels of cable tray at top. The transverse beam elevations as below:
- EL (+) 7.5m – Pipe supporting Level
- EL (+) 11.5m – Pipe supporting Level
- EL (+) 15.5m – Pipe supporting Level
- EL (+) 20.0m – Cable Tray & Grating Level
Column bases of the structure are fixed in transverse direction and pinned in longitudinal direction. The lateral stability of the structure is provided by concentric bracing system in longitudinal bracing and moment resisting frames in transverse direction. Pipe rack is supported on pedestal of height 0.3m above the ground level.
The structure is designed according to AISC 360-10.
Figure 4‑1 3D Isometric View of Pipe Rack
- The analysis and design is performed using STAAD Pro Connect Edition design software.
LOADS AND LOAD COMBINATIONS OF PIPERACKS
DEAD LOAD
Structural Dead load (Ds)
Structural self-weight of modelled steel elements are automatically generated in STAAD Pro
- Structural self-weight of all steel members are computed considering a unit weight of 78.5 kN/m3 multiplied by a contingency factor of 1.2 taking into account for connection details.
- Self-weight of secondary beam and grating is considered as 1.0 kN/m2 and applied as dead load on the structure.
Elevation (m) | Contributory length (m) | Unit Load (kN/m²) | width of walkway | Total (kN) |
(+) 20.000 | 6 | 1 | 0.8 | 2.4 |
Figure 5‑1 Grating load at EL (+) 20.000 m
EMPTY DEAD LOAD (De)
- Empty load of the pipe is considered as 60% of the pipe operating load.
Elevation (m) | Contributory length (m) | Unit Load (kN/m²) | 60% for Empty Load (kN/m²) | Total (kN/m) | Remarks |
(+) 7.50 | 6 | 2 | 1.2 | 7.2 | Piping unit load as per SLD |
(+) 11.50 | 6 | 2.8 | 1.68 | 10.08 | Piping unit load as per SLD |
(+) 15.50 | 6 | 2 | 1.2 | 7.2 | Piping unit load as per SLD |
- Empty Cable tray load is assumed as 10% of cable tray operating load. Considered 600mm wide cable tray for loadings.
Elevation (m) | Unit Load (kN/m²) | 10% for Empty Unit Load (kN/m²) | 600 Wide Tray Load kN/m | No of Trays | Contributory length (m) | Total (kN) | Moment kNm (0.9m cantilever) |
(+) 20.0 | 1.5 | 0.15 | 0.09 | 4 | 6 | 2.16 | 1.944 |
(+) 20.0 | 1.5 | 0.15 | 0.09 | 8 | 6 | 4.32 | – |
Figure 5‑2 Pipe Empty Dead load at EL (+) 7.5m, 11.5m, 15.5m & 20.0 m
PIPE OPERATING LOAD (DO)
- The pipe operating load is considered as per SLD from piping layout.
Elevation (m) | Contributory length (m) | Unit Load (kN/m²) | Total (kN/m) | Remarks |
(+) 7.50 | 6 | 2 | 12 | Piping unit load as per SLD |
(+) 11.50 | 6 | 2.8 | 16.8 | Piping unit load as per SLD |
(+) 15.50 | 6 | 2 | 12 | Piping unit load as per SLD |
- The Cable tray load is considered as 1.5 kN/m2 per level of cable tray in the absence of electrical data. Considered 600mm wide cable tray for loadings.
Elevation (m) | Unit Load (kN/m²) | Cable Operating Load (kN/m) | No of Trays | Contributory length (m) | Total (kN) | Moment kNm (0.8m cantilever) |
(+) 20.0 | 1.5 | 0.9 | 4 | 6 | 21.6 | 17.28 |
(+) 20.0 | 1.5 | 0.9 | 8 | 6 | 43.2 | – |
Figure 5‑3 Pipe Operating load at EL (+) 7.5m, 11.5m, 15.5m & 20.0 m
PIPE TEST LOAD (DT)
- The pipe test load is considered as per SLD from piping layout.
Elevation (m) | Contributory length (m) | Unit Load (kN/m²) | Total (kN/m) | Remarks |
(+) 7.50 | 6 | 2 | 12 | Piping unit load as per SLD |
(+) 11.50 | 6 | 2.8 | 16.8 | Piping unit load as per SLD |
(+) 15.50 | 6 | 2 | 12 | Piping unit load as per SLD |
- The Cable tray load is considered as 1.5 kN/m2 per level of cable tray in the absence of electrical data. Assumed 600 wide cable tray for loadings.
Elevation (m) | Unit Load (kN/m²) | Cable Operating Load (kN/m) | No of Trays | Contributory length (m) | Total (kN) | Moment kNm (0.8m cantilever) |
(+) 20.0 | 1.5 | 0.9 | 4 | 6 | 21.6 | 17.28 |
(+) 20.0 | 1.5 | 0.9 | 8 | 6 | 43.2 | – |
Figure 5‑4 Pipe Test load at EL (+) 7.5m, 11.5m, 15.5m & 20.0 m
LIVE LOAD (LL)
Live load is considered as 2.87 kN/m2 and applied as UDL.
Elevation (m) | Contributory length (m) | Unit Load (kN/m²) | width of walkway | Total (kN) |
(+) 20.00 | 6 | 2.78 | 0.8 | 6.672 |
Figure 5‑5 Live load at EL (+) 20.0 m
THERMAL LOAD (Ts1 & Ts2)
- Temperature load are taken from the Basic Engineering Design Data. The thermal load is considered for the structure with maximum temperature variation of +42°C and minimum temperature variation of 6°C from the ambient temperature.
- Maximum Temperature : 42°C
- Minimum Temperature : 6°C
- Mean Ambient Temperature : 26°C
- TL1 max = 42 – 26 = +16 °C
- TL2 min = 6 – 26 = – 20 °C
Figure 5‑6 Thermal Load showing maximum and minimum temperature
PIPE ANCHOR/GUIDE LOAD (Ttsgu)
- No pipe Anchor/Guide load is considered.
PIPE FRICTION LOAD (TtF)
The 10% of the pipe operating load has been considered as pipe friction load for pipes numbers > 6. The loads are applied in longitudinal direction along the pipe direction.
Elevation (m) | Contributory length (m) | Pipe Operating Load (kN/m²) | 10% for Pipe Operating Load (kN/m²) |
---|---|---|---|
(+) 7.50 | 6 | 2 | 0.2 |
(+) 11.50 | 6 | 2.8 | 0.28 |
(+) 15.50 | 6 | 2 | 0.2 |
Figure 5‑7 Pipe Empty load at EL (+) 4.45 m & EL (+) 6.35 m
WIND LOAD (WLX & WLZ)
Wind Parameters:
Basic wind speed (3sec-gust) = 85.70 m/s
Category = III
F, applied wind force = qz G Cf Af (Eq. 29.5-1), ASCE 7-10
qz – Velocity Pressure at height z above Ground.
G – Gust effect factor
Cf – Net force coefficient
Af – Projected area normal to wind
Velocity Pressure qz:
qz, (N/m2) = 0.613 Kz Kzt Kd V2 (Eq. 30.3-1), ASCE 7 -10
Kz, Velocity pressure exposure coefficient
Kzt, Topographic factor
Kd, Wind directionality factor
V, Basic wind speed (3 sec – Gust) m/s
Exposure Factor = D
H, Height of hill or escarpment = 27 m (Grading level)
Lh, Distance upwind of crest at H/2 = 50 m (shore to escarpment = 100m)
x, Distance from crest to building site = 100 m (escarpment to bldg = 100m)
z, Ht above ground surface at bldg site = 47 m 27+ ht of pipe rack
Considering 2-D escarpments
μ, Horizontal attenuation factor = 4 Figure 26.8-1 (ASCE 7-10) – down wind
γ, Height attenuation factor = 2.5 Figure 26.8-1 (ASCE 7-10)
k1, (k1/(H/Lh) = 0.95 = 0.513
k2, = 0.5
k3, = 0.095
Kzt, = 1.05
Kd, Wind directionality factor = 0.85 Table 26.6-1, ASCE 7-10
G – Gust effect factor = 0.85 26.9.1, ASCE 7-10
Table 5‑2 : wind pressure for height z
Cf – Net force coefficient
Ref: Sec. 4.1, ASCE-Report – Wind Loads and Anchor Bolt Design for Petrochemical Facilities
All structural members = 1.8 uniformly at all tier levels
For Cable tray = 2.0
For Pipes = 0.7 Fig 29.5-1, ASCE 7-10 (smooth pipe)
Wind load Calculated for member with fire proof insulation – X Direction
z, (m) | Member | Member depth | Insulation width | wind expose width “d” | F=qzxGxCf xd, (kN/m) (Per frame) | Direction “X” or “Z” | Elevations in ‘m’ | Remarks |
---|---|---|---|---|---|---|---|---|
5.00 | HE450B | 0.450 | 0.025 | 0.500 | 3.04 | X | 105.000 | Column |
9.50 | HE450B | 0.450 | 0.025 | 0.500 | 3.32 | X | 109.500 | Column |
7.50 | HE400B | 0.400 | 0.025 | 0.450 | 2.99 | X | 105.700 | Beams |
*Fireproof exposed wind area considered upto 9.5m. Above 9m to 20m there is no fire proff so wind loads are applied using staad definition. |
Wind load Calculated for member with fire proof insulation – Z Direction
z, (m) | Member | Member depth | Insulation width | wind expose width “d” | F=qzxGxCf xd, (kN/m) (Per frame) | Direction “X” or “Z” | Elevations in ‘m’ | Remarks |
5.00 | HE450B | 0.300 | 0.025 | 0.350 | 2.13 | Z | 105.000 | Column |
9.50 | HE450B | 0.300 | 0.025 | 0.350 | 2.32 | Z | 109.500 | Column |
5.70 | HE160A | 0.160 | 0.000 | 0.160 | 1.06 | Z | 105.700 | Beams |
5.00 | HE240A | 0.240 | 0.025 | 0.290 | 1.76 | Z | 105.000 | bracing |
9.50 | L130X130 | 0.130 | 0.025 | 0.180 | 1.10 | Z | 109.500 | bracing |
Transverse Wind Force due to Pipe:
Ref: Sec. 4.1, ASCE-Report – Wind Loads and Anchor Bolt Design for Petrochemical Facilities
Tributary Area: Af = (D + 10%W) x Bent Spacing (m)
where, D is maximum pipe diameter at respective level
W is useable width of pipe rack
Force on Pipe: F = qzxGxCfxAf
Z level (m) | Dia. of Pipe – D, (Incl. Insulation thk.) (m) | Useable Width of PR, (m) | Length, (m) | Af, (m2) | F (Per frame) | Direction “X” or “Z” | Elevations in ‘m’ | Remarks |
7.50 | 0.762 | 8.0 | 6.0 | 9.372 | 22.17 | Z | 107.500 | 30dia inch pipe- SLD |
11.50 | 0.762 | 8.0 | 6.0 | 9.372 | 24.21 | Z | 111.500 | 30dia inch pipe- SLD |
15.50 | 1.219 | 8.0 | 6.0 | 12.115 | 31.29 | Z | 115.500 | 48dia inch pipe- SLD |
Transverse Wind Force due to Cable Tray:
Ref: Sec. 4.1, ASCE-Report – Wind Loads and Anchor Bolt Design for Petrochemical Facilities
Tributary Area: Ae = (D + 10%W) x Bent Spacing (m)
where, D is maximum pipe diameter at respective level sss
W is useable width of pipe rack
Force on Pipe: F = qzxGxCfxAf
z, (m) | cable tray height (m) | No of Trays | Usuable Width of PR,(m) | Length, (m) | Af, (m2) | F=qzxGxCfxAe, (kN) (Per frame) | Moment kNm (0.9m ht) | Elevations in ‘m’ |
20.00 | 0.150 | 4.000 | 3.0 | 6.0 | 10.800 | 86.40 | 77.76 | 120.000 |
Figure 5‑8 Wind load in X – Direction
Figure 5‑9 Wind load in Z – Direction
SEISMIC LOAD (SLX/SLZ/SLY)
- Risk Factor = III Table 1.5-1/ASCE-7-10
- Importance Factor, I = 1.25 Table 1.5-2/ASCE-7-10
- Seismic Design Category = C Table 11.6-1/ASCE-7-10
- Response modification coefficient, R
- Steel ordinary braced frame X-Dir = 3.25 Table C15.5-1/ASCE-7-10
- Steel ordinary moment frames Z-Dir = 3.5 Table C15.5-1/ASCE-7-10
- For initial Staad factor in X Dir I/R 0.38
- For initial Staad factor in Z Dir I/R 0.36
- The Site Specific Design Response Spectrum shall be considered from Section 6.7 of project document “Design Specification for Loads and Load Combinations”
Figure 5‑10 Seismic load in X/Z/Y – Direction
SERVICIABILITY LOAD COMBINATION
1 | D | Ds + Do + Ts | Operating Weight + Sustained Thermal (Sustained Load Case for Deflection or Settlement) |
Ds + Do + Ts + Tt | Operating Weight + Sustained Thermal + Temporary Thermal | ||
Ds + Dt + Ts + Tt | Test Weight + Sustained Thermal + Temporary Thermal | ||
2 | D+L | Ds + Do + Ts + L | Operating Weight + Sustained Thermal + Live |
Ds + Dt + Ts + L | Test Weight + Sustained Thermal + Live | ||
3 | D + (Lr or S or R) | N/A | |
4 | D + 0.75 L + 0.75 (Lr or S or R) | Ds + Do + Ts + 0.75 Tt + 0.75 L + 0.75 S | Operating Weight + Sustained Thermal + Temporary Thermal + Live + Snow |
Ds + Dt+ Ts + 0.75 Tt +0.75 L + 0.75 S | Test Weight + Sustained Thermal b + Temporary Thermal + Live + Snow | ||
5 | D + (0.6 W or 0.7 E) | Ds + Do + Ts + 0.6 W | Operating Weight + Sustained Thermal + Wind |
Ds + Do + Ts + 0.7 Eo | Operating Weight + Sustained Thermal + Earthquake | ||
Ds + Dt + Ts + 0.6 Wp | Test Weight + Sustained Thermal + Partial Wind | ||
6a | D + 0.75 L + 0.75 (0.6 W) + 0.75 (Lr or S or R) | Ds + Do + Ts + 0.75 L + 0.75 (0.6 W) + 0.75 S | Operating Weight + Sustained Thermal + Live + Wind + Snow |
Ds + Dt + Ts + 0.75 L +0.75 (0.6 Wp) + 0.75 S | Test Weight + Sustained Thermal + Live + Partial Wind + Snow | ||
6b | D + 0.75 L + 0.75 (0.7 E) +0.75 S | Ds + Do + Ts + 0.75 L + 0.75 (0.7 Eo) + 0.75 S | Operating Weight + Sustained Thermal + Live + Earthquake + Snow |
7 | 0.6 D + 0.6 W | 0.6 (Ds + De) + Ts e,f + 0.6 W | Empty Weight + Sustained Thermal + Wind (Wind Uplift Case) |
0.6 (Ds + Do) + Ts + 0.6 W | Operating Weight + Sustained Thermal + Wind (Sustained Thermal and Wind Uplift Case) | ||
8 | 0.6 D + 0.6 E | 0.6 (Ds + De) + Ts + 0.7 Ee | Empty Weight + Sustained Thermal + Earthquake (Earthquake Uplift Case) |
0.6 (Ds + Do) + Ts + 0.7 Eo | Operating Weight + Sustained Thermal + Earthquake (Sustained Thermal and Earthquake Uplift Case) |
STRENGTH LOAD COMBINATION (LRFD)
1 | 1.4 D | 1.4 (Ds + Do) + 1.2 Ts | Operating Weight + Sustained Thermal |
1.4 (Ds + Dt) + 1.2 Ts | Test Weight + Sustained Thermal | ||
2 | 1.2 D + 1.6 L +0.5 (Lr or S or R) | 1.2 (Ds + Do) + 1.2 Ts + 1.0 Tt +1.6 L + 0.5 S | Operating Weight + Sustained Thermal + Temporary Thermal + Live + Snow |
1.2 (Ds + Dt+ 1.2 Ts+ 1.0 Tt +1.6 L + 0.5 Sd | Test Weight + Sustained Thermal + Temporary Thermal + Live + Snow | ||
3 | 1.2 D + 1.6 (Lr or S or R) + (L or 0.5 W) | 1.2 (Ds + Do) + 1.2 Ts + 1.0 Tt + 1.6 S + 0.5 Le | Operating Weight + Sustained Thermal + Temporary Thermal + Live + Snow |
1.2 (Ds + Do) + 1.2 Ts + 1.6 S + 0.5 W | Operating Weight + Sustained Thermal + Snow + Wind | ||
1.2 (Ds + Dt )+ 1.2 Ts + 1.0 Tt +1.6 Sd + 0.5 Le | Test Weight + Sustained Thermal + Temporary Thermal + Snow + Live | ||
1.2 (Ds + Dt) + 1.2 Ts + 1.6 Sd + 0.5 W | Test Weight + Sustained Thermal + Snow + Wind | ||
4 | 1.2 D + 1.0 W + L + 0.5 (Lr or S or R) | 1.2 (Ds + Do) + 1.2 Ts + 1.0 W + 0.5 Le + 0.5 S | Operating Weight + Sustained Thermal + Wind + Live + Snow |
1.2 (Ds + Dt + 1.2 Ts + 1.0 Wp + 0.5 Le + 0.5 Sd | Test Weight + Sustained Thermal + Partial Wind + Live + Snow | ||
5 | 1.2 D + 1.0 E + L + 0.2 S | 1.2 (Ds + Do) + 1.2 Ts + 1.0 Eo + 0.5 Le + 0.2 S | Operating Weight + Sustained Thermal + Earthquake + Live + Snow |
6 | 0.9 D + 1.0 W | 0.9 (Ds + De) + 1.2 Ts f,g + 1.0 W | Empty Weight + Sustained Thermal + Wind (Wind Uplift Case) |
0.9 (Ds + Do) + 1.2 Ts g + 1.0 W | Operating Weight + Sustained Thermal + Wind (Wind Uplift Case) | ||
7 | N/A | 1.2 (Ds + Do) + 1.2 Ts + 1.2 Tt + 0.5 L + 0.5 S | Operating Weight + Sustained Thermal + Temporary Thermal + Live + Snow |
1.2 (Ds + Dt ) + 1.2 Ts + 1.2 Tt + 0.5 L + 0.5 Sd | Test Weight + Sustained Thermal + Temporary Thermal + Live + Snow |
RESULTS
BEAM DEFLECTION CHECK
- Local deflections of the beams are checked using STAAD software under serviceability load combinations and ensured design is adequate for the limit specified in project document “Design Specification for Steel Structures”
- Pipe rack main beams : L/400
- Pipe rack secondary beams : L/250
- Critical Beam Deflection results:
Member Description | Beam No. | Member Property | LC | UC Ratio | Allowable Ratio | Remarks |
Transverse Bm-1 | 131 | HE360A | 1009 | 0.326 | 1.00 | Safe |
Transverse Bm-2 | 132 | HE400A | 1007 | 0.301 | 1.00 | Safe |
Transverse Bm-3 | 130 | HE450A | 1037 | 0.269 | 1.00 | Safe |
COLUMN DEFLECTION CHECK
WIND DRIFT
- Horizontal displacement at top of columns due to wind is limited to H/100 where H is the total column height.
- Governing Load Case: LC- 1018 (DS+DO+TS2+TTSGU+0.60 WLZ)
Figure 6‑1 Column Drift due to wind along Z Direction- The following table shows the maximum deflection at top of column and relevant ratio:
Elevation Height (m) | Load case | Node | Levels (m) | Drift Height H (m) | Drift Deflection mm | Allowable Deflection mm | Check |
20 | 1018 | 45 | 117.5 | 17.5 | 104.71 | 175 | SAFE |
Table 6‑1 : Horizontal Displacement check due to wind
SEISMIC DRIFT
- Allowable seismic drift limits shall be in accordance with ASCE/SEI 7-10 (Sect.12.8.6). Being the structure assigned to Seismic Category C and Occupancy Category IV, the design story drift shall not exceed hsx/200 (where hsx is the story height below level x).
Figure 6‑2 Column Drift due to seismic along Z Direction- Actual Drift
- Cd*δxe / I < hsx/200
- Where:
- Cd = deflection amplification factor = 3.0 (as per Table 15.4-1) – steel ordinary moment frame;
- δxe = calculated deflection;
- I = importance factor = 1.25 (as per Table 1.5-2)
- Governing Load Case: LC- 1022 (DS+DO+TS2+TTSGU+0.21 SLX+0.70 SLZ+0.21 SLY)
Elevation Height (m) | Load case | Node | Levels (m) | Δ (mm) | Drift Δx (mm) | Actual Drift (mm) | Allowable Deflection (h/200) mm | Check |
20 | 1022 | 45 | 120 | 17.914 | 2.851 | 6.8 | 22.5 | SAFE |
13.5 | 39 | 113.5 | 15.063 | 3.26 | 7.8 | 20 | SAFE | |
10.5 | 47 | 110.5 | 11.803 | 3.956 | 9.5 | 20 | SAFE | |
7.5 | 41 | 107.5 | 7.847 | 7.847 | 18.8 | 37.5 | SAFE |
Table 6‑2 : Seismic Storey drift check
UNITY RATIO
- Design of the structure is performed using STAAD software and ensured member design adequacy. The utility ratios of the members are presented below.
Strength Case: | |||||||||||
Member Description | Beam No. | Member Property | LC | UC Ratio | Allowable Ratio | Remarks | |||||
Column | 116 | HE450B | 123 | 0.89 | 0.90 | Safe | |||||
Transverse Bm-1 | 130 | HE450A | 123 | 0.88 | 0.90 | Safe | |||||
Transverse Bm-2 | 132 | HE400A | 124 | 0.83 | 0.90 | Safe | |||||
Long Bm -1 | 143 | HE200A | 123 | 0.55 | 0.90 | Safe | |||||
Vert Bracings/ Plan Brace | 171 | HE240A | 121 | 0.91 | 0.95 | Safe | |||||
141 | ISA130X130X12 SD | 121 | 0.83 | 0.90 | Safe | ||||||
178 | ISA120X120X12 SD | 122 | 0.80 | 0.90 | Safe | ||||||
180 | ISA90X90X8 SD | 134 | 0.45 | 0.7 | Safe |
Table 6‑3 : Maximum utility ratio of the structure – Strength Case
STAAD UNITY STRESS RATIO
Figure 6‑3 Staad Unity Stress picture
Product categories
- Civil & Structural Design Calculations (30)
- Commercial Plans (3)
- Excel Spread sheets (27)
- House Plans (13)
- Industrial drawing template (7)
- Uncategorized (0)
Recent Posts
- Column Buckling
- Moody Chart | Moment Reactions for Rectangular Plates |
- Test Pile Drawing Calculation & Guidelines
- Commercial Shop Plan
- Shop Floor Plan
- HOUSE PLAN WITH SHOP 40 x 60 | SOUTH FACING |
- Wind Load Calculation as per Australian Code (AS/NZS 1170.2:2021)
- HOUSE PLAN 30 X 45 | EAST FACING | INTERIOR HOUSE DESIGN |
- HOUSE PLAN 60 x 40 | EAST FACING | APARTMENT TYPE |
- Standard Road Details
- DG Building Architectural Plan & Finishing Schedule
- AMAZING TV UNIT IDEAS 90+ MODELS
- HOUSE PLAN 60 x 50 | EAST FACING |
- Technical Details for Wash Basin Section and Elevation
- Tender Technical Specification for Plumbing and Sanitary works
- HOUSE PLAN 25 x 50 | SOUTH FACING |
- HOUSE PLAN 60 x 45 | SOUTH FACING |
- Fencing Gate Details and Requirements
- Fencing Layout and Details For Transformer Area
- Fencing with Angle Post and Pipe Post Details & Arrangements
- Civil Engineering Formula Book | Pocket Guide pdf Free download |
- HOUSE PLAN 35 x 60 | WEST FACING |
- Transformer Foundation with Soak Pit Layout and Details
- Grating Standard Details and Specifications
- Chequered Plate Standard Details
- Handrail Details for Steel Structural Floors
- Cable Pull Pit Requirements and Details
- Laboratory Building Plan and Architecture Details
- Structural Bolt Details Types Grades and Applications
- HOUSE PLAN 40 x 60 | NORTH FACING |
- Finishing Schedule Drawing for Doors, Windows, and Rolling Shutters
- Workshop Building Architectural Layout
- Calculation of Foundation Bearing Capacity as per IS 6403 – 1981
- Terzaghi’s Bearing Capacity Calculation For Foundations
- DESIGN AND CONSTRUCTION METHOD OF MULTISTORY CONCRETE BUILDINGS
- HOUSE PLAN 60 x 60 | SOUTH FACING |
- Civil Structural Engineering Interview Questions pdf Free Download
- Civil Structural Engineering Interview Questions
- HOUSE PLAN 60 x 30 | EAST FACING |
- HOUSE PLAN 28 x 31 | WEST FACING |
- SHEAR FORCE AND BENDING MOMENT DIAGRAMS WITH FORMULA
- HOUSE PLAN 43 x 66 | SOUTH FACING |
- Canadian Code Seismic Calculation Example
- Weathering Course in RCC Roof
- Rolling Shutter Fixing Detail with RCC Beam
- HOUSE PLAN 35 x 50 | SOUTH FACING |
- APARTMENT PLAN 53 x 62 | EAST & WEST Facing |
- Duct Bank Details and Pipe Sleeves Details
- Handrail Details | Construction Methods and Types of Handrail |
- Details of Ramp
- Design Calculation of Steel Shelter – AISC 360
- Cage Ladder Specification and Detail Drawing
- Staircase Ideas 40+
- Vertical Vessel Foundation Design
- Effective Length for RCC Columns
- DESIGN OF SLABS AS PER IS456
- Design of Staircase Waist Slab
- Monorail Beam Design
- HOUSE PLAN 35 x 50 | SOUTH FACING |
- Concrete Beam Design as per Canadian Code (CSA A23.3-19)
- Wind Load Calculation as per Canadian Code | NBCC 2020 |
- Fencing Detail Drawing
- HOUSE PLAN 40 x 60 | NORTH FACING |
- HOUSE PLAN 60 x 30 | SOUTH FACING |
- RCC Fencing Post Details
- HOUSE PLAN 30 x 40 | NORTH FACING |
- HOUSE PLAN 45 x 45 | WEST FACING |
- HOUSE PLAN 40 x 40 | WEST FACING |
- HOUSE PLAN 30 x 50 | SOUTH FACING |
- Modern House Front Elevation Design
- Transformer Foundation Design
- Gypsum Board False Ceiling Installation
- Box Culvert Design
- Design of Anchor Reinforcement in Concrete Pedestals
- Wind Load Calculation for Pipe Rack
- Apartment House Plan | West Facing 60 x 60 |
- kitchen marble design 30+
- Wind Load Calculation as per IS 875 Part 3 2015
- DESIGN BASIS FOR CIVIL AND STRUCTURAL
- General Specification for Civil and Structural Works
- Green Building
- Fireproofing Details
- Response Spectrum Analysis in STAAD pro
- SHELTER WITH 25T CRANE DRAWING | PEB SHED |
- HOUSE PLAN 20 x 60 | WEST FACING |
- MONORAIL DETAILS
- WEST FACING HOUSE PLAN 50 x 40 | DUPLEX TYPE |
- Side Face Reinforcement as per ACI & IS code
- HOUSE PLANS
- HOUSE PLAN 35 x 50 | EAST FACING |
- HOUSE PLAN 25 x 60 | NORTH FACING |
- HOUSE PLAN 35 x 50 | NORTH FACING |
- Design of Cold-Formed Steel Structures as Per IS 801
- HOUSE PLAN 30 x 40 | EAST FACING |
- HOUSE PLAN 30 x 40| NORTH FACING |
- HOUSE PLAN 20 x 40 | NORTH FACING |
- Lifting Padeye Design
- Corbel Design and Details
- DYNAMIC ANALYSIS USING RESPONSE SPECTRUM ANALYSIS
- Building Load Calculation
- Deep Excavations
- Bathroom Tiles Designs Ideas 50+
- Wooden Main Door Ideas 40+
- Gate Design Ideas 60+
- Structural Design of working pile
- Design of Gantry Girder
- Modern Kitchen Interior Idea Photos 26+
- BEHAVIOUR OF STEEL CHIMNEY UNDER DYNAMIC LOADINGS
- Church Design Drawing
- Seismic Load Calculation as per ASCE 7-16
- 33×66 North Facing Ground Floor Plan with Vastu
- DESIGN OF WIND PRESSURE AS PER EN 1991-1-4
- Best 3D House Elevation Design G+1
- House Plan with Photos | Architect Detail Drawing |
- Trench Details
- PRECAST COVER SLAB DETAILS
- Grade Slab Details
- Resort Cottage Plan
- CONCRETE BATCHING PLANT ARRANGEMENT
- LOAD COMBINATIONS NBCC 2023
- STEEL SHED DRAWING
- Plumbing Drawing
- Pre Engineered Building Design Specification IS Code
- SMALL HOUSE PLAN 28 x 40 | NORTH FACING |
- DESIGN OF PIPERACK STRUCTURE
- BATHROOM FIXTURES AND FITTINGS – European Closet, Urinal & Wash Basin
- DUPLEX HOUSE PLAN 30 x 30 | EAST FACING |
- HOUSE PLAN 29 x 44 | EAST FACING | DUPLEX HOUSE
- Design of Pipe Support Foundation Calculation
- FLAT SLAB DESIGN AND DETAILING
- DIRECT ANALYSIS METHOD AISC 360-05 AND ITS IMPLEMENTATION IN STAAD
- PILE FOUNDATION | TYPE OF PILES | TEST METHODS AND SITE EXECUTION |
- HOUSE PLAN 38 x 58 | BEST EAST FACING | HOME THEATER
- Front Elevation Design 30+
- Design of Concrete Anchor Blocks
- HOUSE PLAN WITH OFFICE AT GROUND FLOOR 27 x 88 | NORTH FACING |
- Design of Shear Key in Base Plate as per IS Code
- HOUSE PLAN 45 x 40 | BEST NORTH FACING BUILDING PLAN |
- BANQUET HALL PLAN 40 x 60 | NORTH FACING |
- MARRIAGE HALL PLAN 33 x 77 | SOUTH FACING |
- COMMERCIAL PLAN 48 x 40 | NORTH FACING |
- APARTMENT TYPE HOUSE PLAN 30 x 80 | EAST FACING | 3BHK
- APARTMENT PLAN 40×50 | EAST FACING | 3BHK |
- Concrete Mix Design Calculations
- PEB Shed Drawing
- HOUSE PLAN 40 x 46 | NORTH FACING |
- DEVELOPMENT LENGTH OF REBAR